Liquefied Petroleum Gas Certificate of Conformity

Do you need a Gas CoC? And does your gas installation comply to the standard?
An LPG CoC is necessary for your household insurance, sale of property and bond registration.
We will come out and inspect your installation and issue a CoC once the installation is up to standard as per SANS 10087-1:2024.

 

Areas serviced in Pretoria:

LPG COC Pretoria East , LPG COC Pretoria North , LPG COC Pretoria West , LPG COC Montana , LPG COC Faerie Glen , LPG COC Moreletta Park , LPG COC Centurion , LPG COC Olympus , LPG COC Garsfontein , LPG COC Meyers Park , LPG COC Murrayfield , LPG COC Silver Lakes , LPG COC Lombardy , LPG COC Shere , LPG COC Lynnwood , LPG COC Waterkloof , LPG COC Pierre Van Ryneveld , LPG COC Waverly , LPG COC Villeria , LPG COC Moregloed , LPG COC Bergtuin , LPG COC Queenswood , LPG COC Brooklyn , LPG COC Hatfield , LPG COC Arcadia , LPG COC Pretoria Gardens , LPG COC Booysens , LPG COC Midstream Estates , LPG COC Midstream Meadows , LPG COC Midstream Ridge , LPG COC Midfield , LPG COC Midstream Hill , LPG CO Midstream Heights , LPG COC Midlands , LPG COC Retire @ Midstream , LPG COC Amberfield Heights , LPG COC Amberfield Glen , LPG COC Amberfield Crest , LPG COC Amberfield Ridge , LPG COC Thatchfield Close , LPG COC Thatchfield Hills , LPG COC Thatchfield Crest

Areas serviced in Johannesburg

LPG COC Sandton , LPG COC Rosebank , LPG COC Melrose Arch , LPG COC Parkhurst , LPG COC Roodepoort , LPG COC Randburg , LPG COC Cresta , LPG COC Fourways , LPG COC Honeydew , LPG COC Lonehill , LPG COC Edenvale , LPG COC Linbro Park , LPG COC Bedfordview , LPG COC Glen Vista , LPG COC Meyersdal , LPG COC Alberton , LPG COC Brackenhurst , LPG COC Northcliff , LPG COC Northriding , LPG COC Krugersdorp , LPG COC Ruimsig , LPG COC Parkmore , LPG COC Sandhurst , LPG COC Birch Acres , LPG COC Atlasville , LPG COC Boksburg , LPG COC Rynfield , LPG COC Benoni , LPG COC Brakpan , LPG COC Braamfontein

Quick Contact

1 Step 1
reCaptcha v3
keyboard_arrow_leftPrevious
Nextkeyboard_arrow_right

As its boiling point LPG is below room temperature, it evaporates quickly at normal temperatures thus supplying the needed pressure within the vessel to have your appliance operating correctly. It is also supplied in pressurized steel vessels, normally called LPG cylinders.

Get a LPG COC

Do you already have an LPG Gas installation but you don’t know if its legal? Compare it to the following diagrams or give us a call to make sure.

Outside Installation


Containers shall be at least


Doors, Windows & Airbricks

1 m away from  any  opening  (into  a  building)  that  is  below  the  level  of  the  container  valve, ie. a) doors, windows and airbricks,b) 2 m away from any drain, pit or manhole,

3 m away  from  the  property  boundary wall,  unless  the  boundary  has  a  firewall,  in  which  case  the  containers  could  be  next  to  the  firewall and  where  there  are  only  two  containers,  the boundary distance can be reduced to 1 m, and,

3 m away from any opening (or window) directly above the containers. The 3 m distance from the top of the cylinder, valve connection or the manifold whichever is the higher, to the bottom of the window(s) may be reduced to a minimum of 300 mm providing that the cylinders are in a cage with a steel roof-top.

Roofs 

4) a non-combustible  roof  (see  SANS  10400)  is  installed  between  the  containers  and  the    The  roof  shall  extend  beyond  the  cylinder(s)  such  that  when  measured  from  the  valve connection and around the roof to the nearest point of the window a minimum of 1,5 m safety distance shall be obtained, or

5) the window  frames  shall  be  steel  and  the  total  size  of  the  glazing  does  not  exceed  1  Glazing  shall  be  of  wire  woven  glass  not  larger  than  450  mm  ×  450  mm  per  pane.  Such windows shall not be openable.

6) where a roof  is  installed  over  the  cylinders  there  shall  be  sufficient  space  above  the  cylinder  valves  to  facilitate  the  exchange  of  Roof structures of concrete shall not be installed above the manifold or cylinder

Electrical Points

7) 5m away from a switchable electrical point i.e. plug socket, Inline power isolator, Aircon units, Pool pumps, Water pumps etc. Note, a wall light only needs to be 1.5m to the left/right of the bottles, or 1.5m above the bottles.

Read more about regulations